4900 Pt100 133.2 (requires option M16.8)

No. Setting Range Factory

setting

Description

4901 Pt100 133.2 Set point -49 to 482 °C 80 °C Three different input types are

4902 Pt100 133.2 Timer 0.0 to 600.0 s 120.0 s

available with Option M16.8:

• 4-20 mA

4903 Pt100 133.2 Relay output A Not used (option Not used

• 0-5 V

dependent)

• Pt100

4904 Pt100 133.2 Relay output B Not used (option Not used

The value shown in this

dependent)

parameter group is available

4905 Pt100 133.2 Enable OFF

ON

OFF

when Pt100 is selected in

parameter 11190.

4906 Pt100 133.2 Fail class F1 to F9 F2 (Warning)

4910 Wire fail 133 (requires option M16.8)

No. Setting Range Factory

setting

Description

4911 Wire fail ana

133

4912 Wire fail ana

133

Relay output A

Relay output B

Not used (option

dependent)

Not used (option

dependent)

Not used

Not used

For function description of wire

fail, see the Option M16

manual.

4913 Wire fail ana

133

Enable

OFF

ON

OFF

4914

Wire fail ana

133

Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 89 of 222