Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
4870 4-20 mA 131.2 (requires option M16.8)
No. Setting Range Factory
setting
Description
4871 4-20 mA
131.2
4872
4-20 mA
131.2
4873 4-20 mA
131.2
4874 4-20 mA
131.2
4875 4-20 mA
131.2
Set point 4 to 20 mA 10 mA Three different input types are
available with Option M16.8:
Timer 0.0 to 600.0 s 120.0 s
Relay output A
Relay output B
Enable
Not used (option
dependent)
Not used (option
dependent)
OFF
ON
Not used
Not used
OFF
• 4-20 mA
• 0-5 V
• Pt100
The value shown in this
parameter group is available
when 4-20 mA is selected in
parameter 11180.
4876
4-20 mA
131.2
Fail class F1 to F9 F2 (Warning)
4870 V DC 131.2 (requires option M16.8)
No. Setting Range Factory
setting
Description
4871 V DC 131.2 Set point 0 to 5 V 2 V Three different input types are
4872 V DC 131.2 Timer 0.0 to 600.0 s 120.0 s
available with Option M16.8:
• 4-20 mA
4873 V DC 131.2 Relay output A Not used (option Not used
• 0-5 V
dependent)
• Pt100
4874 V DC 131.2 Relay output B Not used (option Not used
The value shown in this
dependent)
parameter group is available
4875 V DC 131.2 Enable OFF
ON
OFF
when 0-5 V is selected in
parameter 11180.
4876 V DC 131.2 Fail class F1 to F9 F2 (Warning)
4870 Pt100 131.2 (requires option M16.8)
No. Setting Range Factory
setting
Description
4871 Pt100 131.2 Set point -49 to 482 °C 80 °C Three different input types are
4872 Pt100 131.2 Timer 0.0 to 600.0 s 120.0 s
available with Option M16.8:
• 4-20 mA
4873 Pt100 131.2 Relay output A Not used (option Not used
• 0-5 V
dependent)
• Pt100
4874 Pt100 131.2 Relay output B Not used (option Not used
The value shown in this
dependent)
parameter group is available
4875 Pt100 131.2 Enable OFF
ON
OFF
when Pt100 is selected in
parameter 11180.
4876 Pt100 131.2 Fail class F1 to F9 F2 (Warning)
PARAMETER LIST 4189340688R EN Page 86 of 222