4040 Pt100 93.2 (requires option M16.6)

No. Setting Range Factory

setting

Description

4041 Pt100 93.2 Set point -49 to 482 °C 80 °C Three different input types are

4042 Pt100 93.2 Timer 0.0 to 600.0 s 120.0 s

available with Option M16.6:

• 4-20 mA

4043 Pt100 93.2 Relay output A Not used (option Not used

• 0-5 V

dependent)

• Pt100

4044 Pt100 93.2 Relay output B Not used (option Not used

The value shown in this

dependent)

parameter group is available

4045 Pt100 93.2 Enable OFF

ON

OFF

when Pt100 is selected in

parameter 11130.

4046 Pt100 93.2 Fail class F1 to F9 F2 (Warning)

4050 Wire fail 93 (requires option M16.6)

No. Setting Range Factory

setting

Description

4051 Wire fail ana

93

4052 Wire fail ana

93

Relay output A

Relay output B

Not used (option

dependent)

Not used (option

dependent)

Not used

Not used

For function description of wire

fail, see the Option M16

manual.

4053 Wire fail ana

93

Enable

OFF

ON

OFF

4054

Wire fail ana

93

Fail class F1 to F9 F2 (Warning)

4060 4-20 mA 95.1 (requires option M16.6)

No. Setting Range Factory

setting

Description

4061 4-20 mA 95.1 Set point 4 to 20 mA 10 mA Three different input types are

4062 4-20 mA 95.1 Timer 0.0 to 600.0 s 120.0 s

available with Option M16.6:

• 4-20 mA

4063 4-20 mA 95.1 Relay output A Not used (option Not used

• 0-5 V

dependent)

• Pt100

4044 4-20 mA 95.1 Relay output B Not used (option Not used

The value shown in this

dependent)

parameter group is available

4065 4-20 mA 95.1 Enable OFF

ON

OFF

when 4-20 mA is selected in

parameter 11140.

4066 4-20 mA 95.1 Fail class F1 to F9 F2 (Warning)