4020 Wire fail 91 (requires option M16.6)

No. Setting Range Factory

setting

Description

4021 Wire fail ana

91

4022 Wire fail ana

91

Relay output A

Relay output B

Not used (option

dependent)

Not used (option

dependent)

Not used

Not used

For function description of wire

fail, see the Option M16

manual.

4023 Wire fail ana

91

Enable

OFF

ON

OFF

4024

Wire fail ana

91

Fail class F1 to F9 F2 (Warning)

4030 4-20 mA 93.1 (requires option M16.6)

No. Setting Range Factory

setting

Description

4031 4-20 mA 93.1 Set point 4 to 20 mA 10 mA Three different input types are

4032 4-20 mA 93.1 Timer 0.0 to 600.0 s 120.0 s

available with Option M16.6:

• 4-20 mA

4033 4-20 mA 93.1 Relay output A Not used (option Not used

• 0-5 V

dependent)

• Pt100

4034 4-20 mA 93.1 Relay output B Not used (option Not used

The value shown in this

dependent)

parameter group is available

4035 4-20 mA 93.1 Enable OFF

ON

OFF

when 4-20 mA is selected in

parameter 11130.

4036 4-20 mA 93.1 Fail class F1 to F9 F2 (Warning)

4030 V DC 93.1 (requires option M16.6)

No. Setting Range Factory

setting

Description

4031 V DC 93.1 Set point 0 to 5 V 2 V Three different input types are

4032 V DC 93.1 Timer 0.0 to 600.0 s 120.0 s

available with Option M16.6:

• 4-20 mA

4033 V DC 93.1 Relay output A Not used (option Not used

• 0-5 V

dependent)

• Pt100

4034 V DC 93.1 Relay output B Not used (option Not used

The value shown in this

dependent)

parameter group is available

4035 V DC 93.1 Enable OFF

ON

OFF

when 0-5 V is selected in

parameter 11130.

4036 V DC 93.1 Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 73 of 222