You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
4010 4-20 mA 91.2 (requires option M16.6)
No. Setting Range Factory
setting
Description
4011 4-20 mA 91.2 Set point 4 to 20 mA 10 mA Three different input types are
4012 4-20 mA 91.2 Timer 0.0 to 600.0 s 120.0 s
available with Option M16.6:
• 4-20 mA
4013 4-20 mA 91.2 Relay output A Not used (option Not used
• 0-5 V
dependent)
• Pt100
4014 4-20 mA 91.2 Relay output B Not used (option Not used
The value shown in this
dependent)
parameter group is available
4015 4-20 mA 91.2 Enable OFF
ON
OFF
when 4-20 mA is selected in
parameter 11120.
4016 4-20 mA 91.2 Fail class F1 to F9 F2 (Warning)
4010 V DC 91.2 (requires option M16.6)
No. Setting Range Factory
setting
Description
4011 V DC 91.2 Set point 0 to 5 V 2 V Three different input types are
4012 V DC 91.2 Timer 0.0 to 600.0 s 120.0 s
available with Option M16.6:
• 4-20 mA
4013 V DC 91.2 Relay output A Not used (option Not used
• 0-5 V
dependent)
• Pt100
4014 V DC 91.2 Relay output B Not used (option Not used
The value shown in this
dependent)
parameter group is available
4015 V DC 91.2 Enable OFF
ON
OFF
when 0-5 V is selected in
parameter 11120.
4016 V DC 91.2 Fail class F1 to F9 F2 (Warning)
4010 Pt100 91.2 (requires option M16.6)
No. Setting Range Factory
setting
Description
4011 Pt100 91.2 Set point -49 to 482 °C 80 °C Three different input types are
4012 Pt100 91.2 Timer 0.0 to 600.0 s 120.0 s
available with Option M16.6:
• 4-20 mA
4013 Pt100 91.2 Relay output A Not used (option Not used
• 0-5 V
dependent)
• Pt100
4014 Pt100 91.2 Relay output B Not used (option Not used
The value shown in this
dependent)
parameter group is available
4015 Pt100 91.2 Enable OFF
ON
OFF
when Pt100 is selected in
parameter 11120.
4016 Pt100 91.2 Fail class F1 to F9 F2 (Warning)
PARAMETER LIST 4189340688R EN Page 72 of 222