04.01.2023 Views

agc-4-parameter-list-4189340688-uk

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

4860 4-20 mA 131.1 (requires option M15.8)

No. Setting Range Factory

setting

Description

4861 4-20 mA

131.1

4862

4-20 mA

131.1

Set point 4 to 20 mA 10 mA Configurable analogue input.

Option M15.8: 4 x 4-20 mA

inputs.

Timer 0.0 to 600.0 s 120.0 s

4863 4-20 mA

131.1

Relay output A

Not used (option

dependent)

Not used

4864 4-20 mA

131.1

Relay output B

Not used (option

dependent)

Not used

4865 4-20 mA

131.1

Enable

OFF

ON

OFF

4866

4-20 mA

131.1

Fail class F1 to F9 F2 (Warning)

4870 4-20 mA 131.2 (requires option M15.8)

No. Setting Range Factory

setting

Description

4871 4-20 mA

131.2

4872

4-20 mA

131.2

Set point 4 to 20 mA 10 mA Configurable analogue input.

Option M15.8: 4 x 4-20 mA

inputs.

Timer 0.0 to 600.0 s 120.0 s

4873 4-20 mA

131.2

Relay output A

Not used (option

dependent)

Not used

4874 4-20 mA

131.2

Relay output B

Not used (option

dependent)

Not used

4875 4-20 mA

131.2

Enable

OFF

ON

OFF

4876

4-20 mA

131.2

Fail class F1 to F9 F2 (Warning)

4880 Wire fail 4-20 mA 131 (requires option M15.8)

No. Setting Range Factory

setting

Description

4881 Wire fail ana

131

4882 Wire fail ana

131

4883 Wire fail ana

131

Relay output A

Relay output B

Enable

Not used (option

dependent)

Not used (option

dependent)

OFF

ON

Not used

Not used

OFF

The wire fault will detect if the

current drops below 2 mA or

exceeds 22 mA. In both cases

the alarm will be activated.

Option M15.8: 4 x 4-20 mA

inputs.

4884

Wire fail ana

131

Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 69 of 222

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!