YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

4830 4-20 mA 129.1 (requires option M15.8)

No. Setting Range Factory

setting

Description

4831 4-20 mA

129.1

4832

4-20 mA

129.1

Set point 4 to 20 mA 10 mA Configurable analogue input.

Option M15.8: 4 x 4-20 mA

inputs.

Timer 0.0 to 600.0 s 120.0 s

4833 4-20 mA

129.1

Relay output A

Not used (option

dependent)

Not used

4834 4-20 mA

129.1

Relay output B

Not used (option

dependent)

Not used

4835 4-20 mA

129.1

Enable

OFF

ON

OFF

4836

4-20 mA

129.1

Fail class F1 to F9 F2 (Warning)

4840 4-20 mA 129.2 (requires option M15.8)

No. Setting Range Factory

setting

Description

4841 4-20 mA

129.2

4842

4-20 mA

129.2

Set point 4 to 20 mA 10 mA Configurable analogue input.

Option M15.8: 4 x 4-20 mA

inputs.

Timer 0.0 to 600.0 s 120.0 s

4843 4-20 mA

129.2

Relay output A

Not used (option

dependent)

Not used

4844 4-20 mA

129.2

Relay output B

Not used (option

dependent)

Not used

4845 4-20 mA

129.2

Enable

OFF

ON

OFF

4846

4-20 mA

129.2

Fail class F1 to F9 F2 (Warning)

4850 Wire fail 4-20 mA 129 (requires option M15.8)

No. Setting Range Factory

setting

Description

4851 Wire fail ana

129

4852 Wire fail ana

129

4853 Wire fail ana

129

Relay output A

Relay output B

Enable

Not used (option

dependent)

Not used (option

dependent)

OFF

ON

Not used

Not used

OFF

The wire fault will detect if the

current drops below 2 mA or

exceeds 22 mA. In both cases

the alarm will be activated.

Option M15.8: 4 x 4-20 mA

inputs.

4854

Wire fail ana

129

Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 68 of 222