2.6.2 Analogue input setup (requires option M15.8)

4800 4-20 mA 127.1 (requires option M15.8)

No. Setting Range Factory

setting

Description

4801 4-20 mA

127.1

4802

4-20 mA

127.1

Set point 4 to 20 mA 10 mA Configurable analogue input.

Option M15.8: 4 x 4-20 mA

inputs.

Timer 0.0 to 600.0 s 120.0 s

4803 4-20 mA

127.1

Relay output A

Not used (option

dependent)

Not used

4804 4-20 mA

127.1

Relay output B

Not used (option

dependent)

Not used

4805 4-20 mA

127.1

Enable

OFF

ON

OFF

4806

4-20 mA

127.1

Fail class F1 to F9 F2 (Warning)

4810 4-20 mA 127.2 (requires option M15.8)

No. Setting Range Factory

setting

Description

4811 4-20 mA

127.2

4812

4-20 mA

127.2

Set point 4 to 20 mA 10 mA Configurable analogue input.

Option M15.8: 4 x 4-20 mA

inputs.

Timer 0.0 to 600.0 s 120.0 s

4813 4-20 mA

127.2

Relay output A

Not used (option

dependent)

Not used

4814 4-20 mA

127.2

Relay output B

Not used (option

dependent)

Not used

4815 4-20 mA

127.2

Enable

OFF

ON

OFF

4816

4-20 mA

127.2

Fail class F1 to F9 F2 (Warning)

4820 Wire fail 4-20 mA 127 (requires option M15.8)

No. Setting Range Factory

setting

Description

4821 Wire fail ana

127

4822 Wire fail ana

127

4823 Wire fail ana

127

Relay output A

Relay output B

Enable

Not used (option

dependent)

Not used (option

dependent)

OFF

ON

Not used

Not used

OFF

The wire fault will detect if the

current drops below 2 mA or

exceeds 22 mA. In both cases

the alarm will be activated.

Option M15.8: 4 x 4-20 mA

inputs.

4824

Wire fail ana

127

Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 67 of 222