4090 4-20 mA 97.1 (requires option M15.6)

No. Setting Range Factory

setting

Description

4091 4-20 mA 97.1 Set point 4 to 20 mA 10 mA Configurable analogue input.

4092 4-20 mA 97.1 Timer 0.0 to 600.0 s 120.0 s

Option M15.6: 4 x 4-20 mA

inputs.

4093 4-20 mA 97.1 Relay output A Not used (option

dependent)

Not used

4094 4-20 mA 97.1 Relay output B Not used (option

dependent)

4095 4-20 mA 97.1 Enable OFF

ON

Not used

OFF

4096 4-20 mA 97.1 Fail class F1 to F9 F2 (Warning)

4100 4-20 mA 97.2 (requires option M15.6)

No. Setting Range Factory

setting

Description

4101 4-20 mA 97.2 Set point 4 to 20 mA 10 mA Configurable analogue input.

4102 4-20 mA 97.2 Timer 0.0 to 600.0 s 120.0 s

Option M15.6: 4 x 4-20 mA

inputs.

4103 4-20 mA 97.2 Relay output A Not used (option

dependent)

Not used

4104 4-20 mA 97.2 Relay output B Not used (option

dependent)

4105 4-20 mA 97.2 Enable OFF

ON

Not used

OFF

4106 4-20 mA 97.2 Fail class F1 to F9 F2 (Warning)

4110 Wire fail 4-20 mA 97 (requires option M15.6)

No. Setting Range Factory

setting

Description

4111 Wire fail ana

97

4112 Wire fail ana

97

4113 Wire fail ana

97

Relay output A

Relay output B

Enable

Not used (option

dependent)

Not used (option

dependent)

OFF

ON

Not used

Not used

OFF

The wire fault will detect if the

current drops below 2 mA or

exceeds 22 mA. In both cases

the alarm will be activated.

Option M15.6: 4 x 4-20 mA

inputs.

4114

Wire fail ana

97

Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 66 of 222