4060 4-20 mA 95.1 (requires option M15.6)

No. Setting Range Factory

setting

Description

4061 4-20 mA 95.1 Set point 4 to 20 mA 10 mA Configurable analogue input.

4062 4-20 mA 95.1 Timer 0.0 to 600.0 s 120.0 s

Option M15.6: 4 x 4-20 mA

inputs.

4063 4-20 mA 95.1 Relay output A Not used (option

dependent)

Not used

4064 4-20 mA 95.1 Relay output B Not used (option

dependent)

4065 4-20 mA 95.1 Enable OFF

ON

Not used

OFF

4066 4-20 mA 95.1 Fail class F1 to F9 F2 (Warning)

4070 4-20 mA 95.2 (requires option M15.6)

No. Setting Range Factory

setting

Description

4071 4-20 mA 95.2 Set point 4 to 20 mA 10 mA Configurable analogue input.

4072 4-20 mA 95.2 Timer 0.0 to 600.0 s 120.0 s

Option M15.6: 4 x 4-20 mA

inputs.

4073 4-20 mA 95.2 Relay output A Not used (option

dependent)

Not used

4074 4-20 mA 95.2 Relay output B Not used (option

dependent)

4075 4-20 mA 95.2 Enable OFF

ON

Not used

OFF

4076 4-20 mA 95.2 Fail class F1 to F9 F2 (Warning)

4080 Wire fail 4-20 mA 95 (requires option M15.6)

No. Setting Range Factory

setting

Description

4081 Wire fail ana

95

4082 Wire fail ana

95

4083 Wire fail ana

95

Relay output A

Relay output B

Enable

Not used (option

dependent)

Not used (option

dependent)

OFF

ON

Not used

Not used

OFF

The wire fault will detect if the

current drops below 2 mA or

exceeds 22 mA. In both cases

the alarm will be activated.

Option M15.6: 4 x 4-20 mA

inputs.

4084

Wire fail ana

95

Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 65 of 222