04.01.2023 Views

agc-4-parameter-list-4189340688-uk

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

4030 4-20 mA 93.1 (requires option M15.6)

No. Setting Range Factory

setting

Description

4031 4-20 mA 93.1 Set point 4 to 20 mA 10 mA Configurable analogue input.

4032 4-20 mA 93.1 Timer 0.0 to 600.0 s 120.0 s

Option M15.6: 4 x 4-20 mA

inputs.

4033 4-20 mA 93.1 Relay output A Not used (option

dependent)

Not used

4034 4-20 mA 93.1 Relay output B Not used (option

dependent)

4035 4-20 mA 93.1 Enable OFF

ON

Not used

OFF

4036 4-20 mA 93.1 Fail class F1 to F9 F2 (Warning)

4040 4-20 mA 93.2 (requires option M15.6)

No. Setting Range Factory

setting

Description

4041 4-20 mA 93.2 Set point 4 to 20 mA 10 mA Configurable analogue input.

4042 4-20 mA 93.2 Timer 0.0 to 600.0 s 120.0 s

Option M15.6: 4 x 4-20 mA

inputs.

4043 4-20 mA 93.2 Relay output A Not used (option

dependent)

Not used

4044 4-20 mA 93.2 Relay output B Not used (option

dependent)

4045 4-20 mA 93.2 Enable OFF

ON

Not used

OFF

4046 4-20 mA 93.2 Fail class F1 to F9 F2 (Warning)

4050 Wire fail 4-20 mA 93 (requires option M15.6)

No. Setting Range Factory

setting

Description

4051 Wire fail ana

93

4052 Wire fail ana

93

4053 Wire fail ana

93

Relay output A

Relay output B

Enable

Not used (option

dependent)

Not used (option

dependent)

OFF

ON

Not used

Not used

OFF

The wire fault will detect if the

current drops below 2 mA or

exceeds 22 mA. In both cases

the alarm will be activated.

Option M15.6: 4 x 4-20 mA

inputs.

4054

Wire fail ana

93

Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 64 of 222

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!