2.6 Input/output parameters: Analogue input setup

2.6.1 Analogue input setup (requires option M15.6)

4000 4-20 mA 91.1 (requires option M15.6)

No. Setting Range Factory

setting

Description

4001 4-20 mA 91.1 Set point 4 to 20 mA 10 mA Configurable analogue input.

4002 4-20 mA 91.1 Timer 0.0 to 600.0 s 120.0 s

Option M15.6: 4 x 4-20 mA

inputs.

4003 4-20 mA 91.1 Relay output A Not used (option

dependent)

Not used

4004 4-20 mA 91.1 Relay output B Not used (option

dependent)

4005 4-20 mA 91.1 Enable OFF

ON

Not used

OFF

4006 4-20 mA 91.1 Fail class F1 to F9 F2 (Warning)

4010 4-20 mA 91.2 (requires option M15.6)

No. Setting Range Factory

setting

Description

4011 4-20 mA 91.2 Set point 4 to 20 mA 10 mA Configurable analogue input.

4012 4-20 mA 91.2 Timer 0.0 to 600.0 s 120.0 s

Option M15.6: 4 x 4-20 mA

inputs.

4013 4-20 mA 91.2 Relay output A Not used (option

dependent)

Not used

4014 4-20 mA 91.2 Relay output B Not used (option

dependent)

4015 4-20 mA 91.2 Enable OFF

ON

Not used

OFF

4016 4-20 mA 91.2 Fail class F1 to F9 F2 (Warning)

4020 Wire fail 4-20 mA 91 (requires option M15.6)

No. Setting Range Factory

setting

Description

4021 Wire fail ana

91

4022 Wire fail ana

91

4023 Wire fail ana

91

Relay output A

Relay output B

Enable

Not used (option

dependent)

Not used (option

dependent)

OFF

ON

Not used

Not used

OFF

The wire fault will detect if the

current drops below 2 mA or

exceeds 22 mA. In both cases

the alarm will be activated.

Option M15.6: 4 x 4-20 mA

inputs.

4024

Wire fail ana

91

Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 63 of 222