04.01.2023 Views

agc-4-parameter-list-4189340688-uk

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

3480 Digital input 117

No. Setting Range Factory

setting

Description

3481 Dig input 117 Timer 0.0 to 100.0 s 10.0 s The input is configurable.

3482 Dig input 117 Relay output A Not used (option

dependent)

3483 Dig input 117 Relay output B Not used (option

dependent)

3484 Dig input 117 Enable OFF

ON

Not used

Not used

OFF

3485 Dig input 117 Fail class F1 to F9 F2 (Warning)

3486 Dig input 117 High alarm

OFF

ON

ON

2.5.6 Emergency stop

3490 Emergency stop

No. Setting Range Factory

setting

Description

3491 Emer. stop Timer 0.0 to 60.0 s 0.0 s Emergency stop input is

intended for a normally closed

3492 Emer. stop Relay output A Not used (option Not used

contact.

dependent)

3493 Emer. stop Relay output B Not used (option

dependent)

3494 Emer. stop Enable OFF

ON

3495 Emer. stop Fail class F1 to F9

Not used

ON

F5

(Shutdown)

2.5.7 Digital input 127-133 setup (requires option M13.8)

3500 Digital input 127 (requires option M13.8)

No. Setting Range Factory

setting

Description

3501 Dig input 127 Timer 0.0 to 100.0 s 10.0 s The input is configurable.

3502 Dig input 127 Relay output A Not used (option

dependent)

3503 Dig input 127 Relay output B Not used (option

dependent)

3504 Dig input 127 Enable OFF

ON

Not used

Not used

OFF

3505 Dig input 127 Fail class F1 to F9 F2 (Warning)

3506 Dig input 127 High alarm

OFF

ON

ON

PARAMETER LIST 4189340688R EN Page 58 of 222

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!