3420 Digital input 108

No. Setting Range Factory

setting

3421 Wire fail 108 Enable OFF

ON

OFF

3422 Dig input 108 Timer 0.0 to 100.0 s 10.0 s

3423 Dig input 108 Relay output A Not used (option

dependent)

Not used

Description

The input is configurable (only

available if multi-input 108 is

configured to "binary" in menu

11000).

3424 Dig input 108 Relay output B Not used (option

dependent)

3425 Dig input 108 Enable OFF

ON

Not used

OFF

3426 Dig input 108 Fail class F1 to F9 F2 (Warning)

2.5.5 Digital input 112-117 setup

3430 Digital input 112

No. Setting Range Factory

setting

Description

3431 Dig input 112 Timer 0.0 to 100.0 s 10.0 s The input is configurable.

3432 Dig input 112 Relay output A Not used (option

dependent)

3433 Dig input 112 Relay output B Not used (option

dependent)

3434 Dig input 112 Enable OFF

ON

Not used

Not used

OFF

3435 Dig input 112 Fail class F1 to F9 F2 (Warning)

3436 Dig input 112 High alarm

OFF

ON

ON

3440 Digital input 113

No. Setting Range Factory

setting

Description

3441 Dig input 113 Timer 0.0 to 100.0 s 10.0 s The input is configurable.

3442 Dig input 113 Relay output A Not used (option

dependent)

3443 Dig input 113 Relay output B Not used (option

dependent)

3444 Dig input 113 Enable OFF

ON

Not used

Not used

OFF

3445 Dig input 113 Fail class F1 to F9 F2 (Warning)

3446 Dig input 113 High alarm

OFF

ON

ON

PARAMETER LIST 4189340688R EN Page 56 of 222