3390 Digital input 97 (requires option M13.6)

No. Setting Range Factory

setting

Description

3391 Dig input 97 Timer 0.0 to 100.0 s 10.0 s The input is configurable.

3392 Dig input 97 Relay output A Not used (option

dependent)

3393 Dig input 97 Relay output B Not used (option

dependent)

3394 Dig input 97 Enable OFF

ON

Not used

Not used

OFF

3395 Dig input 97 Fail class F1 to F9 F2 (Warning)

3396 Dig input 97 High alarm

OFF

ON

ON

2.5.4 Digital input 102-108 setup

3400 Digital input 102

No. Setting Range Factory

setting

3401 Wire fail 102 Enable OFF

ON

OFF

3402 Dig input 102 Timer 0.0 to 100.0 s 10.0 s

3403 Dig input 102 Relay output A Not used (option

dependent)

Not used

Description

The input is configurable (only

available if multi-input 102 is

configured to "binary" in menu

10980).

3404 Dig input 102 Relay output B Not used (option

dependent)

3405 Dig input 102 Enable OFF

ON

Not used

OFF

3406 Dig input 102 Fail class F1 to F9 F2 (Warning)

3410 Digital input 105

No. Setting Range Factory

setting

3411 Wire fail 105 Enable OFF

ON

OFF

3412 Dig input 105 Timer 0.0 to 100.0 s 10.0 s

3413 Dig input 105 Relay output A Not used (option

dependent)

Not used

Description

The input is configurable (only

available if multi-input 105 is

configured to "binary" in menu

10990).

3414 Dig input 105 Relay output B Not used (option

dependent)

3415 Dig input 105 Enable OFF

ON

Not used

OFF

3416 Dig input 105 Fail class F1 to F9 F2 (Warning)