3230 Digital input 53 (requires option M12)

No. Setting Range Factory

setting

Description

3231 Dig input 53 Timer 0.0 to 100.0 s 10.0 s The input is configurable.

3232 Dig input 53 Relay output A Not used (option

dependent)

3233 Dig input 53 Relay output B Not used (option

dependent)

3234 Dig input 53 Enable OFF

ON

Not used

Not used

OFF

3235 Dig input 53 Fail class F1 to F9 F2 (Warning)

3236 Dig input 53 High alarm

OFF

ON

ON

3240 Digital input 54 (requires option M12)

No. Setting Range Factory

setting

Description

3241 Dig input 54 Timer 0.0 to 100.0 s 10.0 s The input is configurable.

3242 Dig input 54 Relay output A Not used (option

dependent)

3243 Dig input 54 Relay output B Not used (option

dependent)

3244 Dig input 54 Enable OFF

ON

Not used

Not used

OFF

3245 Dig input 54 Fail class F1 to F9 F2 (Warning)

3246 Dig input 54 High alarm

OFF

ON

ON

3250 Digital input 55 (requires option M12)

No. Setting Range Factory

setting

Description

3251 Dig input 55 Timer 0.0 to 100.0 s 10.0 s The input is configurable.

3252 Dig input 55 Relay output A Not used (option

dependent)

3253 Dig input 55 Relay output B Not used (option

dependent)

3254 Dig input 55 Enable OFF

ON

Not used

Not used

OFF

3255 Dig input 55 Fail class F1 to F9 F2 (Warning)

3256 Dig input 55 High alarm

OFF

ON

ON

PARAMETER LIST 4189340688R EN Page 52 of 222