04.01.2023 Views

agc-4-parameter-list-4189340688-uk

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

3170 Digital input 47 (requires option M12)

No. Setting Range Factory

setting

Description

3171 Dig input 47 Timer 0.0 to 100.0 s 10.0 s The input is configurable.

3172 Dig input 47 Relay output A Not used (option

dependent)

3173 Dig input 47 Relay output B Not used (option

dependent)

3174 Dig input 47 Enable OFF

ON

Not used

Not used

OFF

3175 Dig input 47 Fail class F1 to F9 F2 (Warning)

3176 Dig input 47 High alarm

OFF

ON

ON

3180 Digital input 48 (requires option M12)

No. Setting Range Factory

setting

Description

3181 Dig input 48 Timer 0.0 to 100.0 s 10.0 s The input is configurable.

3182 Dig input 48 Relay output A Not used (option

dependent)

3183 Dig input 48 Relay output B Not used (option

dependent)

3184 Dig input 48 Enable OFF

ON

Not used

Not used

OFF

3185 Dig input 48 Fail class F1 to F9 F2 (Warning)

3186 Dig input 48 High alarm

OFF

ON

ON

3190 Digital input 49 (requires option M12)

No. Setting Range Factory

setting

Description

3191 Dig input 49 Timer 0.0 to 100.0 s 10.0 s The input is configurable.

3192 Dig input 49 Relay output A Not used (option

dependent)

3193 Dig input 49 Relay output B Not used (option

dependent)

3194 Dig input 49 Enable OFF

ON

Not used

Not used

OFF

3195 Dig input 49 Fail class F1 to F9 F2 (Warning)

3196 Dig input 49 High alarm

OFF

ON

ON

PARAMETER LIST 4189340688R EN Page 50 of 222