3030 Digital input 26

No. Setting Range Factory

setting

Description

3031 Dig input 26 Timer 0.0 to 100.0 s 10.0 s The input is configurable.

Input 26 is by default used for

3032 Dig input 26 Relay output A Not used (option Not used

breaker feedback (only

dependent)

available in an AGC-4 Mains

3033 Dig input 26 Relay output B Not used (option

dependent)

Not used controller if no TB is present in

the application).

3034 Dig input 26 Enable OFF

ON

OFF

3035 Dig input 26 Fail class F1 to F9 F2 (Warning)

3036 Dig input 26 High alarm

OFF

ON

ON

3040 Digital input 27

No. Setting Range Factory

setting

Description

3041 Dig input 27 Timer 0.0 to 100.0 s 10.0 s The input is configurable.

Input 27 is by default used for

3042 Dig input 27 Relay output A Not used (option Not used

breaker feedback (only

dependent)

available in an AGC-4 Mains

3043 Dig input 27 Relay output B Not used (option

dependent)

Not used controller if no TB is present in

the application).

3044 Dig input 27 Enable OFF

ON

OFF

3045 Dig input 27 Fail class F1 to F9 F2 (Warning)

3046 Dig input 27 High alarm

OFF

ON

ON

2.5.2 Digital input 43-55 setup (requires option M12)

3130 Digital input 43 (requires option M12)

No. Setting Range Factory

setting

Description

3131 Dig input 43 Timer 0.0 to 100.0 s 10.0 s The input is configurable.

3132 Dig input 43 Relay output A Not used (option

dependent)

3133 Dig input 43 Relay output B Not used (option

dependent)

3134 Dig input 43 Enable OFF

ON

Not used

Not used

OFF

3135 Dig input 43 Fail class F1 to F9 F2 (Warning)

3136 Dig input 43 High alarm

OFF

ON

ON

PARAMETER LIST 4189340688R EN Page 48 of 222