Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
3030 Digital input 26
No. Setting Range Factory
setting
Description
3031 Dig input 26 Timer 0.0 to 100.0 s 10.0 s The input is configurable.
Input 26 is by default used for
3032 Dig input 26 Relay output A Not used (option Not used
breaker feedback (only
dependent)
available in an AGC-4 Mains
3033 Dig input 26 Relay output B Not used (option
dependent)
Not used controller if no TB is present in
the application).
3034 Dig input 26 Enable OFF
ON
OFF
3035 Dig input 26 Fail class F1 to F9 F2 (Warning)
3036 Dig input 26 High alarm
OFF
ON
ON
3040 Digital input 27
No. Setting Range Factory
setting
Description
3041 Dig input 27 Timer 0.0 to 100.0 s 10.0 s The input is configurable.
Input 27 is by default used for
3042 Dig input 27 Relay output A Not used (option Not used
breaker feedback (only
dependent)
available in an AGC-4 Mains
3043 Dig input 27 Relay output B Not used (option
dependent)
Not used controller if no TB is present in
the application).
3044 Dig input 27 Enable OFF
ON
OFF
3045 Dig input 27 Fail class F1 to F9 F2 (Warning)
3046 Dig input 27 High alarm
OFF
ON
ON
2.5.2 Digital input 43-55 setup (requires option M12)
3130 Digital input 43 (requires option M12)
No. Setting Range Factory
setting
Description
3131 Dig input 43 Timer 0.0 to 100.0 s 10.0 s The input is configurable.
3132 Dig input 43 Relay output A Not used (option
dependent)
3133 Dig input 43 Relay output B Not used (option
dependent)
3134 Dig input 43 Enable OFF
ON
Not used
Not used
OFF
3135 Dig input 43 Fail class F1 to F9 F2 (Warning)
3136 Dig input 43 High alarm
OFF
ON
ON
PARAMETER LIST 4189340688R EN Page 48 of 222