2.5 Input/output parameters: Binary input setup
2.5.1 Digital input 23-27 setup
3000 Digital input 23
No. Setting Range Factory
setting
Description
3001 Dig input 23 Timer 0.0 to 100.0 s 10.0 s The input is configurable.
3002 Dig input 23 Relay output A Not used (option
dependent)
3003 Dig input 23 Relay output B Not used (option
dependent)
3004 Dig input 23 Enable OFF
ON
Not used
Not used
OFF
3005 Dig input 23 Fail class F1 to F9 F2 (Warning)
3006 Dig input 23 High alarm
OFF
ON
ON
3010 Digital input 24
No. Setting Range Factory
setting
Description
3011 Dig input 24 Timer 0.0 to 100.0 s 10.0 s The input is configurable.
Input 24 is by default used for
3012 Dig input 24 Relay output A Not used (option Not used
breaker feedback (only
dependent)
available if no MB is present in
3013 Dig input 24 Relay output B Not used (option
dependent)
Not used the application).
3014 Dig input 24 Enable OFF
ON
OFF
3015 Dig input 24 Fail class F1 to F9 F2 (Warning)
3016 Dig input 24 High alarm
OFF
ON
ON
3020 Digital input 25
No. Setting Range Factory
setting
Description
3021 Dig input 25 Timer 0.0 to 100.0 s 10.0 s The input is configurable.
Input 25 is by default used for
3022 Dig input 25 Relay output A Not used (option Not used
breaker feedback (only
dependent)
available if no MB is present in
3023 Dig input 25 Relay output B Not used (option
dependent)
Not used the application).
3024 Dig input 25 Enable OFF
ON
OFF
3025 Dig input 25 Fail class F1 to F9 F2 (Warning)
3026 Dig input 25 High alarm
OFF
ON
ON
PARAMETER LIST 4189340688R EN Page 47 of 222