2630 De-load error

No. Setting Range Factory

setting

Description

2631 De-load error Timer 0.0 to 60.0 s 10.0 s The alarm is activated if the

generator fails to de-load within

2632 De-load error Relay output A Not used (option Not used

the delay time.

dependent)

2633 De-load error Relay output B Not used (option

dependent)

Not used

2634 De-load error Enable

OFF

ON

ON

2635 De-load error Fail class F1 to F9 F2 (Warning)

2680 AVR regulation failure (with option D1)

No. Setting Range Factory

setting

Description

2681 AVR reg fail Set point 1.0 to 100.0 % 30.0 % The alarm is activated if the

2682 AVR reg fail Timer 10.0 to 300.0 s 60.0 s

difference between the

measured value and the set

2683 AVR reg fail Relay output A Not used (option

dependent)

Not used point is outside the deadband

for longer than the delay time.

2684 AVR reg fail Relay output B Not used (option

dependent)

Not used

2685 AVR reg fail Fail class F1 to F9 F2 (Warning)