2.4 Control parameters: Regulation

2.4.1 Regulation alarms

2300 Section P> (with option T1)

No. Setting Range Factory

setting

Description

2301 Section P> MW 0 to 30000 MW 0 MW Short-circuit limitation: Used to

2302 Section P> kW 0 to 999 kW 0 kW

limit the power on the busbar in

a power management system.

2303 Section P> Delay 0 to 999 s 1 s

2304 Section P> Relay output A Not used (option

dependent)

2305 Section P> Enable OFF

ON

Not used

2306 Section P> Fail class F1 to F9 F2 (Warning)

OFF

Set point in menus 2301 and

2302 are used as limit value for

max. allowed power in the

system.

These values are all common

set point in the power

management system.

2310 Section P> (with option T1)

No. Setting Range Factory

setting

Description

2311 Section P> Factor 1.0 to 25.5 1.0 This value is used as a

weighing factor for the P NOM

value kW of each transformer

or generator in the power

management system (in case

of two equally sized).

2560 Governor regulation failure

No. Setting Range Factory

setting

Description

2561 Gov. reg fail Deadband 1.0 to 100.0 % 30.0 % The alarm is activated if the

2562 Gov. reg fail Timer 10.0 to 300.0 s 60.0 s

difference between the

measured value and the set

2563 Gov. reg fail Relay output A Not used (option

dependent)

Not used point is outside the deadband

for longer than the delay time.

2564 Gov. reg fail Relay output B Not used (option

dependent)

Not used

2565 Gov. reg fail Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 45 of 222