2270 Close before excitation failure

No. Setting Range Factory

setting

Description

2271 Close before

exc. fail

2272 Close before

exc. fail

2273 Close before

exc. fail

2274 Close before

exc. fail

Timer 0.0 to 999.0 s 5.0 s This alarm will occur if the

generator and breaker are not

Relay output A

Relay output B

Enable

Not used (option

dependent)

Not used (option

dependent)

OFF

ON

Not used

Not used

ON

operating within the limits of

the Close Before Excitation.

The alarm will open the

generator breaker and enable

the regulation synchronising

the generator in a normal way.

2275

Close before

exc. fail

Fail class F1 to F9 F2 (Warning)

2.3.2 Mains sync. inhibit

2280 Mains sync. inhibit settings

No. Setting Range Factory

setting

Description

2281 Mains sync.

inh. U

2282 Mains sync.

inh. U

2283 Mains sync.

inh. F

2284 Mains sync.

inh. F

Low limit U 80 to 100 % 85 % This function is used to inhibit

the synchronising of the mains

High limit U 100 to 120 % 110 %

breaker after blackout.

Low limit F 90 to 100 % 95 %

High limit F 100 to 110 % 101 %

2285

Mains sync.

inh.

Enable

OFF

ON

OFF

2286

Mains sync.

inh.

Fail class F1 to F9 F3 (Trip GB)

2290 Mains sync. inhibit recovery settings

No. Setting Range Factory

setting

Description

2291 Delay act. re2 Recovery sel. timer 0 to 20 s 3 s After blackout, the timer in

menu 2291 will start to run, and

2292 Recovery Delay time 0 to 60 s 5 s

if the mains voltage and

delay 1

frequency are inside the

2293 Recovery

delay 1

Relay output A Not used (option

dependent)

Not used tolerance ranges (menus

2281-2282) before the timer

runs out, the short interruption

2294 Recovery Delay time 0 to 2000 s 600 s

timer (menu 2292) will be

delay 2

started.

2295

Recovery

delay 2

Relay output A

Not used (option

dependent)

Not used

When the timers have run out,

the synchronising of MB will

start.

PARAMETER LIST 4189340688R EN Page 43 of 222