04.01.2023 Views

agc-4-parameter-list-4189340688-uk

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

2.3 Control parameters: Synchronisation

2.3.1 Synchronisation and breaker alarms

2120 Synchronisation window

No. Setting Range Factory

setting

Description

2121 Sync. window Set point 2.0 to 20.0 % 15.0 % The alarm will activate if the

2122 Sync. window Timer 0.1 to 2.0 s 0.5 s

actual voltage deviates from

nominal voltage with the set

2123 Sync. window Relay output A Not used (option

dependent)

Not used percentage.

2124 Sync. window Relay output B Not used (option

dependent)

2125 Sync. window Enable OFF

ON

Not used

OFF

2130 GB/TB/BTB breaker synchronisation failure

No. Setting Range Factory

setting

Description

2131 GB/TB/BTB

sync. failure

2132 GB/TB/BTB

sync. failure

Timer 5.0 to 999.9 s 60.0 s The controller has

unsuccessfully tried to

Relay output A

Not used (option

dependent)

Not used

synchronise the breaker to the

busbar within the delay time.

2133 GB/TB/BTB

sync. failure

Relay output B

Not used (option

dependent)

Not used

2134 GB/TB/BTB

sync. failure

Enable

OFF

ON

OFF

2135

GB/TB/BTB

sync. failure

Fail class F1 to F9 F1 (Block)

2140 Mains breaker synchronisation failure

No. Setting Range Factory

setting

Description

2141 MB sync.

failure

2142 MB sync.

failure

Timer 5.0 to 999.9 s 60.0 s The controller has

unsuccessfully tried to

Relay output A

Not used (option

dependent)

Not used

synchronise the breaker to the

busbar within the delay time.

2143 MB sync.

failure

Relay output B

Not used (option

dependent)

Not used

2144 MB sync.

failure

Enable

OFF

ON

ON

2145

MB sync.

failure

Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 40 of 222

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!