1980 GB/MB external trip

No. Setting Range Factory

setting

1981 GB ext. trip Enable OFF

ON

1982 GB ext. trip Fail class F1 to F9 F2 (Warning)

ON

Description

The generator breaker or the

mains breaker has been

tripped by an external device.

1983 MB ext. trip Enable OFF

ON

ON

1984 MB ext. trip Fail class F1 to F9 F2 (Warning)

1990 Minimum current and minimum Phi angle (with option A1)

No. Setting Range Factory

setting

Description

1991 U and Q< 1: I

Min. 1

1992 U and Q< 1:

Angle 1

1993

U and Q< 2: I

Min. 2

Set point

Set point

Set point

0 to 20 %

0 to 6 °

0 to 20 %

0 %

0 °

0 %

Settings relate to U and Q<

parameters 1960 and 1970.

Condition for "U and Q<" trip is

that the current exceeds the I

Min. set point. Min. Phi angle

expands the tripping window.

1994

U and Q< 2:

Angle 2

Set point 0 to 6 ° 0 °

PARAMETER LIST 4189340688R EN Page 39 of 222