2.2.21 Non-essential load trip (load shedding)

INFO

Setting values relate to the nominal settings.

1800 NEL 1 over-current

No. Setting Range Factory

setting

Description

1801 NEL 1 I> Set point 50.0 to 200.0 % 100.0 % Trip of non-essential load due

1802 NEL 1 I> Timer 0.1 to 100.0 s 5.0 s

to over-current. This function

activates NEL group 1.

1803 NEL 1 I> Enable OFF

ON

OFF

1810 NEL 2 over-current

No. Setting Range Factory

setting

Description

1811 NEL 2 I> Set point 50.0 to 200.0 % 100.0 % Trip of non-essential load due

1812 NEL 2 I> Timer 0.1 to 100.0 s 8.0 s

to over-current. This function

activates NEL group 2.

1813 NEL 2 I> Enable OFF

ON

OFF

1820 NEL 3 over-current

No. Setting Range Factory

setting

Description

1821 NEL 3 I> Set point 50.0 to 200.0 % 100.0 % Trip of non-essential load due

1822 NEL 3 I> Timer 0.1 to 100.0 s 10.0 s

to over-current. This function

activates NEL group 3.

1823 NEL 3 I> Enable OFF

ON

OFF

1830 NEL 1 busbar under-frequency

No. Setting Range Factory

setting

Description

1831 NEL 1 bus f< Set point 70.0 to 100.0 % 95.0 % Trip of non-essential load due

1832 NEL 1 bus f< Timer 0.1 to 100.0 s 5.0 s

to low frequency. This function

activates NEL group 1.

1833 NEL 1 bus f< Enable OFF

ON

OFF

1840 NEL 2 busbar under-frequency

No. Setting Range Factory

setting

Description

1841 NEL 2 bus f< Set point 70.0 to 100.0 % 95.0 % Trip of non-essential load due

1842 NEL 2 bus f< Timer 0.1 to 100.0 s 8.0 s

to low frequency. This function

activates NEL group 2.

1843 NEL 2 bus f< Enable OFF

ON

OFF

PARAMETER LIST 4189340688R EN Page 36 of 222