1650 Time-dependent under-voltage 1 activation (with option A1)

No. Setting Range Factory

setting

Description

1651

1652

1653

Ut< act 1

Ut< act 1

Ut< act 1

Activate

Recovery

Delay

30.0 to 120.0 %

30.0 to 120.0 %

0.0 to 320.0 s

90.0 %

95.0 %

1.0 s

Activate is the voltage value

where the function timer starts.

Reset is the value where the

function timer is reset to 0 ms.

Delay is the delay timer for the

1654 Ut< act 1 Relay output A Not used (option Not used

reset. The relay outputs will

dependent)

activate immediately when the

1655 Ut< act 1 Relay output B Not used (option Not used function timer starts.

dependent)

1656 Ut< act 1 Enable OFF

ON

OFF

Configuration of LVRT curve is

done with the Utility Software in

“Advanced Protection”.

1660 Time-dependent under-voltage 1 (with option A1)

No. Setting Range Factory

setting

Description

1661 Ut< 1 Relay output A Not used (option

dependent)

1662 Ut< 1 Relay output B Not used (option

dependent)

Not used

Not used

The alarm and fail class is

activated instantaneously when

the voltage value is under the

programmed value curve.

1663 Ut< 1 Enable OFF

ON

1664 Ut< 1 Fail class F1 to F9 F6 (Trip MB)

OFF

Configuration of LVRT curve is

done with the Utility Software in

“Advanced Protection”.

INFO

Parameter groups 1670 and 1680 are outdated. Configure the LVRT curve in the Utility Software (under Advanced

Protection).

1690 Time-dependent under-voltage 2 activation (with option A1)

No. Setting Range Factory

setting

Description

1691

1692

1693

Ut< act 2

Ut< act 2

Ut< act 2

Activate

Recovery

Delay

30.0 to 120.0 %

30.0 to 120.0 s

0.0 to 320.0 s

90.0 %

95.0 %

1.0 s

Activate is the voltage value

where the function timer starts.

Reset is the value where the

function timer is reset to 0 ms.

Delay is the delay timer for the

1694 Ut< act 2 Relay output A Not used (option Not used

reset. The relay outputs will

dependent)

activate immediately when the

1695 Ut< act 2 Relay output B Not used (option Not used function timer starts.

dependent)

1696 Ut< act 2 Enable OFF

ON

OFF

Configuration of LVRT curve is

done with the Utility Software in

“Advanced Protection”.

PARAMETER LIST 4189340688R EN Page 34 of 222