2.2.15 Directional over-current protections

1600 Directional over-current 1 (with option A5)

No. Setting Range Factory

setting

Description

1601

1602

1603

I> direct 1

I> direct 1

I> direct 1

Set point

Timer

Relay output A

-200.0 to 200.0 %

0.0 to 100.0 s

Not used (option

dependent)

120.0 %

0.1 s

Not used

Settings relate to nominal

current. The alarm and fail

class are activated when the

directional current has been

continuously above the

1604 I> direct 1 Relay output B

programmed value during the

Not used (option Not used

programmed delay.

dependent)

1605 I> direct 1 Enable OFF

ON

1606 I> direct 1 Fail class F1 to F9 F6 (Trip MB)

OFF

The current measurement is

positive when current is

supplied from the mains to the

plant. The current

measurement is negative when

current is being supplied to the

mains.

1610 Directional over-current 2 (with option A5)

No. Setting Range Factory

setting

Description

1611

1612

1613

I> direct 2

I> direct 2

I> direct 2

Set point

Timer

Relay output A

-200.0 to 200.0 %

0.0 to 100.0 s

Not used (option

dependent)

130.0 %

0.1 s

Not used

Settings relate to nominal

current. The alarm and fail

class are activated when the

directional current has been

continuously above the

1614 I> direct 2 Relay output B

programmed value during the

Not used (option Not used

programmed delay.

dependent)

1615 I> direct 2 Enable OFF

ON

1616 I> direct 2 Fail class F1 to F9 F6 (Trip MB)

OFF

The current measurement is

positive when current is

supplied from the mains to the

plant. The current

measurement is negative when

current is being supplied to the

mains.

PARAMETER LIST 4189340688R EN Page 32 of 222