2.2.12 Reactive power export (over-excitation) protection

1530 Reactive power export (over-excitation)

No. Setting Range Factory

setting

Description

1531 Q> Set point 0.0 to 100.0 % 60.0 % Settings relate to nominal

1532 Q> Timer 0.1 to 100.0 s 10.0 s

power. The alarm and fail class

are activated when exported

1533 Q> Relay output A Not used (option Not used var has been continuously

1534 Q> Relay output B

dependent)

Not used (option

dependent)

Not used

above the programmed value

during the programmed delay.

1535 Q> Enable OFF

ON

OFF

1536 Q> Fail class F1 to F9 F2 (Warning)

2.2.13 Negative sequence

1540 Negative sequence current (with option C2)

No. Setting Range Factory

setting

Description

1541 Negative seq.

I

1542 Negative seq.

I

1543 Negative seq.

I

Set point 1.0 to 100.0 % 20.0 % Settings relate to nominal

current. The alarm and fail

Timer 0.2 to 100.0 s 0.5 s

Relay output A

Not used (option

dependent)

Not used

class are activated when the

negative sequence has been

continuously above the

programmed value during the

programmed delay.

1544 Negative seq.

I

Relay output B

Not used (option

dependent)

Not used

1545 Negative seq.

I

Enable

OFF

ON

OFF

1546 Negative seq.

I

Fail class F1 to F9 F6 (Trip MB)

1550 G/M/BA negative sequence voltage (with option C2)

No. Setting Range Factory

setting

Description

1551 G/M/BA neg.

seq. U

1552 G/M/BA neg.

seq. U

1553 G/M/BA neg.

seq. U

Set point 1.0 to 100.0 % 5.0 % Settings relate to nominal

voltage. The alarm and fail

Timer 0.2 to 100.0 s 0.5 s

Relay output A

Not used (option

dependent)

Not used

class are activated when the

negative sequence has been

continuously above the

programmed value during the

programmed delay.

1554 G/M/BA neg.

seq. U

Relay output B

Not used (option

dependent)

Not used

1555 G/M/BA neg.

seq. U

Enable

OFF

ON

OFF

1556 G/M/BA neg.

seq. U

Fail class F1 to F9 F6 (Trip MB)

PARAMETER LIST 4189340688R EN Page 30 of 222