1710 unbalanced current 2

No. Setting Range Factory

setting

Description

1711 Unbalance

current 2

Set point 0.0 to 50.0 % 10.0 % Settings relate to nominal

generator current.

1712 Unbalance

current 2

1713 Unbalance

current 2

1714 Unbalance

current 2

1715 Unbalance

current 2

1716 Unbalance

current 2

Timer 0.1 to 100.0 s 10.0 s

Relay output A

Relay output B

Enable

Not used (option

dependent)

Not used (option

dependent)

OFF

ON

Not used

Not used

OFF

Fail class F1 to F9 F3 (Trip GB)

The alarm and fail class are

activated when the difference

between the max. reading and

the min. reading of the 3

measured currents has been

continuously above the

programmed value during the

programmed delay.

2.2.10 Voltage unbalance protections

1510 unbalanced voltage

No. Setting Range Factory

setting

Description

1511 Unbalance

voltage

Set point 0.0 to 50.0 % 10.0 % Settings relate to nominal

generator voltage.

1512 Unbalance

voltage

1513 Unbalance

voltage

1514 Unbalance

voltage

1515 Unbalance

voltage

1516 Unbalance

voltage

Timer 0.1 to 100.0 s 10.0 s

Relay output A

Relay output B

Enable

Not used (option

dependent)

Not used (option

dependent)

OFF

ON

Not used

Not used

OFF

Fail class F1 to F9 F3 (Trip GB)

The alarm and fail class are

activated when the difference

between the max. reading and

the min. reading of the 3

measured voltages has been

continuously above the

programmed value during the

programmed delay.

2.2.11 Reactive power import (loss of excitation) protection

1520 Reactive power import (loss of excitation)

No. Setting Range Factory

setting

Description

1521 –Q> Set point 0.0 to 150.0 % 50.0 % Settings relate to nominal

1522 –Q> Timer 0.1 to 100.0 s 10.0 s

power. The alarm and fail class

are activated when imported

1523 –Q> Relay output A Not used (option Not used var has been continuously

1524 –Q> Relay output B

dependent)

Not used (option

dependent)

Not used

above the programmed value

during the programmed delay.

1525 –Q> Enable OFF

ON

OFF

1526 –Q> Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 29 of 222