1410 Busbar under-frequency 4

No. Setting Range Factory

setting

Description

1411

1412

1413

BB f< 4

BB f< 4

BB f< 4

Set point

Timer

Relay output A

80.0 to 100.0 %

0.0 to 99.99 s

Not used (option

dependent)

95.0 %

5.0 s

Not used

The alarm and fail class are

activated when the frequency

has been continuously under

the programmed value during

the programmed delay.

1414 BB f< 4 Relay output B Not used (option

dependent)

1415 BB f< 4 Enable OFF

ON

Not used

OFF

With option A10: Timer

maximum is 2000.0 s.

1416 BB f< 4 Fail class F1 to F9 F2 (Warning)

1920 Busbar over-frequency 4

No. Setting Range Factory

setting

Description

1921 BB f> 4 Set point 100.0 to 120.0 % 102.0 % The alarm and fail class are

1922 BB f> 4 Timer 1500 to 6000 s 5600 s

activated when the frequency

has been continuously above

1923 BB f> 4 Relay output A Not used (option

dependent)

Not used the programmed value during

the programmed delay.

1924 BB f> 4 Relay output B Not used (option

dependent)

1925 BB f> 4 Enable OFF

ON

Not used

OFF

1926 BB f> 4 Fail class F1 to F9 F2 (Warning)

1930 Busbar under-frequency 5

No. Setting Range Factory

setting

Description

1931 BB f< 5 Set point 80.0 to 100.0 % 95.0 % The alarm and fail class are

1932 BB f< 5 Timer 1500 to 6000 s 5600 s

activated when the frequency

has been continuously under

1933 BB f< 5 Relay output A Not used (option

dependent)

Not used the programmed value during

the programmed delay.

1934 BB f< 5 Relay output B Not used (option

dependent)

1935 BB f< 5 Enable OFF

ON

Not used

OFF

1936 BB f< 5 Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 24 of 222