5880 f output (requires option E2, F1 or EF2)

No. Setting Range Factory

setting

5881 f output Transducer A Disabled

Option dependent

5882 f output Transducer B

Disabled

Option dependent

Disabled

Disabled

5883 f output Set point See description Disabled

5884 f output Max. value 0.0 to 70.0 Hz 55.0 Hz

Description

Set point:

• Disabled

• 0-20 mA

• 4-20 mA

• 0-10 V

• -10-0-10 V

5885 f output Min. value 0.0 to 70.0 Hz 45.0 Hz

5890 U output (requires option E2, F1 or EF2)

No. Setting Range Factory

setting

Description

5891 U output Transducer A Disabled

Option dependent

Disabled

The voltage output represents

L1-L2 voltage.

5892 U output Transducer B

Disabled

Option dependent

Disabled

5893 U output Set point See description Disabled

5894 U output Max. value 0 to 28,000 V* 500 V*

5895 U output Min. value 0 to 28,000 V* 0 V

Set point:

• Disabled

• 0-20 mA

• 4-20 mA

• 0-10 V

• -10-0-10 V

*Voltage range and default

depend on the scaling set in

parameter 9030.

5900 I output (requires option E2, F1 or EF2)

No. Setting Range Factory

setting

Description

5901 I output Transducer A Disabled

Option dependent

Disabled

The current output represents

L1 current.

5902 I output Transducer B

Disabled

Option dependent

Disabled

5903 I output Set point See description Disabled

5904 I output Max. value 0 to 9000 A 1000 A

5905 I output Min. value 0 to 9000 A 0 A

Set point:

• Disabled

• 0-20 mA

• 4-20 mA

• 0-10 V

• -10-0-10 V

PARAMETER LIST 4189340688R EN Page 214 of 222