4.5 Transducer outputs

5820 P output 1 (requires option E2, F1 or EF2)

No. Setting Range Factory

setting

5821 P output 1 Transducer A Disabled

Option dependent

5822 P output 1 Transducer B

Disabled

Option dependent

Disabled

Disabled

5823 P output 1 Set point See description Disabled

5824 P output 1 Max. value 0 to 20,000 kW* 500 kW*

Description

Set point:

• Disabled

• 0-20 mA

• 4-20 mA

• 0-10 V

• -10-0-10 V

5825 P output 1 Min. value -9999 to 20,000 kW* 0 kW

*Power range and default

depend on the scaling set in

parameter 9030.

5830 P output 2 (requires option E2, F1 or EF2)

No. Setting Range Factory

setting

5831 P output 2 Transducer A Disabled

Option dependent

5832 P output 2 Transducer B

Disabled

Option dependent

Disabled

Disabled

5833 P output 2 Set point See description Disabled

5834 P output 2 Max. value 0 to 20,000 kW* 500 kW*

Description

Set point:

• Disabled

• 0-20 mA

• 4-20 mA

• 0-10 V

• -10-0-10 V

5835 P output 2 Min. value -9999 to 20,000 kW* 0 kW

*Power range and default

depend on the scaling set in

parameter 9030.

5840 P output 3 (requires option E2, F1 or EF2)

No. Setting Range Factory

setting

5841 P output 3 Transducer A Disabled

Option dependent

5842 P output 3 Transducer B

Disabled

Option dependent

Disabled

Disabled

5843 P output 3 Set point See description Disabled

5844 P output 3 Max. value 0 to 20,000 kW* 500 kW*

Description

Set point:

• Disabled

• 0-20 mA

• 4-20 mA

• 0-10 V

• -10-0-10 V

5845 P output 3 Min. value -9999 to 20,000 kW* 0 kW

*Power range and default

depend on the scaling set in

parameter 9030.

PARAMETER LIST 4189340688R EN Page 212 of 222