4.4.2 Analogue output limits

5720 PWM 68 limits (requires option EF5)

No. Setting Range Factory

setting

Description

5721 PWM 68

limits

Min. 0 to 50 % 10 % For Caterpillar engines.

5722

PWM 68

limits

Max. 50 to 100 % 90 %

5780 AOut 66 limits (requires option E1/E2)

No. Setting Range Factory

setting

Description

5781

5782

AOut 66 limits

AOut 66 limits

Min.

Max.

-25 to 10 mA

10 to 25 mA

-20 mA

20 mA

Option: 2 x analogue outputs

(E1/E2).

Min. range and factory setting

value are option dependent.

5790 AOut 71 limits (requires option E1/E2)

No. Setting Range Factory

setting

Description

5791

5792

AOut 71 limits

AOut 71 limits

Min.

Max.

-25 to 10 mA

10 to 25 mA

-20 mA

20 mA

Option: 2 x analogue outputs

(E1/E2).

Min. range and factory setting

value are option dependent.

5800 AOut 91 limits (requires option F1)

No. Setting Range Factory

setting

Description

5801

5802

AOut 91 limits

AOut 91 limits

Min.

Max.

0 to 10 mA

10 to 20 mA

0 mA

20 mA

Option: 2 x analogue outputs

(F1).

Min. range and factory setting

value are option dependent.

5810 AOut 95 limits (requires option F1)

No. Setting Range Factory

setting

Description

5811

5812

AOut 95 limits

AOut 95 limits

Min.

Max.

0 to 10 mA

10 to 20 mA

0 mA

20 mA

Option: 2 x analogue outputs

(F1).

Min. range and factory setting

value are option dependent.

PARAMETER LIST 4189340688R EN Page 211 of 222