04.01.2023 Views

agc-4-parameter-list-4189340688-uk

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

5140 Relay 63 (requires option M12)

No. Setting Range Factory

setting

Description

5141 Relay 63 Function Alarm relay ND

Limit relay

Horn relay

Siren relay

Alarm relay NE

Alarm relay

ND

5142 Relay 63 OFF delay 0.0 to 999.9 s 5.0 s

5150 Relay 65

No. Setting Range Factory

setting

Description

5151 Relay 65 Function Alarm relay ND

Limit relay

Horn relay

Siren relay

Alarm relay NE

Alarm relay

ND

Used for GOV UP command if

Relay is selected in parameter

2781.

5152 Relay 65 OFF delay 0.0 to 999.9 s 5.0 s

5160 Relay 67

No. Setting Range Factory

setting

Description

5161 Relay 67 Function Alarm relay ND

Limit relay

Horn relay

Siren relay

Alarm relay NE

Alarm relay

ND

Used for GOV DOWN

command if Relay is selected

in parameter 2781.

5162 Relay 67 OFF delay 0.0 to 999.9 s 5.0 s

5170 Relay 69

No. Setting Range Factory

setting

Description

5171 Relay 69 Function Alarm relay ND

Limit relay

Horn relay

Siren relay

Alarm relay NE

Alarm relay

ND

Used for AVR UP command if

Relay is selected in parameter

2783.

5172 Relay 69 OFF delay 0.0 to 999.9 s 5.0 s

5180 Relay 71

No. Setting Range Factory

setting

Description

5181 Relay 71 Function Alarm relay ND

Limit relay

Horn relay

Siren relay

Alarm relay NE

Alarm relay

ND

Used for AVR DOWN

command if Relay is selected

in parameter 2783.

5182 Relay 71 OFF delay 0.0 to 999.9 s 5.0 s

PARAMETER LIST 4189340688R EN Page 207 of 222