2810 AVR limiting
No. Setting Range Factory
setting
Description
2811 AVR limiting Limit type OFF
Droop curve
Capability curve Q
Droop curve
Capability curve limiting
requires option C2.
2812 AVR limiting Set point 20 to 100 % 95 %
The limiting set point is for
Capability curve limiting (which
requires option C2).
2820 Reactive power ramp
No. Setting Range Factory
setting
Description
2821 Q ramp to
setp.
2822
Q ramp to
zero
Ramp up slope
Ramp down slope
0.1 to 20.0 %/s
0.1 to 20.0 %/s
2 %/s
2 %/s
Activation of this will allow the
reactive power to be ramped
up and down, to stabilise the
system.
2823 Q ramp Enable
OFF
ON
OFF
2950 Base load
No. Setting Range Factory
setting
Description
2951 Base load Power set 10.0 to 120.0 % 90 % Setting and enabling of base
load running (base load is only
OFF
2952 Base load Enable
OFF
possible in semi auto mode).
ON
2953 Base load Return mode
Semi-auto mode
Auto mode
Auto mode
The return mode after base
load is completed is specified
in parameter 2953.
2960 Warm up ramp
No. Setting Range Factory
setting
2960 Warm up type Set point Option dependent Multi-input
102
2961
Warm up
thresh.
2962 Warm up type Enable
Set point 0 to 482 ° 0 °
OFF
ON
OFF
Description
When the function input is
activated, it ramps to the set
point from Power ramp up
(parameter 2612) and disables
the Power ramp up function.
When the input is set low
again, it ramps beyond the
limitation.
7290 Frequency offset
No. Setting Range Factory setting Description
7291 f offset Tmax 0 to 2.5 Hz 0 Hz For testing, a frequency offset can be
7292 f offset Tmin -2.5 to 0 Hz 0 Hz
created for stand-alone genset
regulation, using a 4 to 20 mA signal.
7293 f offset meas
Multi input 102 (transducer)
Multi input 102
Multi input 105 (transducer)
(transducer)
Multi input 108 (transducer)