No. Setting Range Factory

setting

Description

only available with option E1,

E2, EF2, EF4 or F2.

2784 Man. step AVR 0.1 to 10.0 s 5.0 s

This timer is used to define

how long the AVR up/down

pulse should be, by activating

an AOP button or a digital

input.

2790 EIC speed demand switch (requires option H5)

No. Setting Range Factory

setting

Description

2791 EIC speed

dem. sw.

2792

EIC speed

dem. sw.

Local norm sw.

Local emerg. sw.

Analogue CAN

Up/Down ECU

Up/Down CAN

Analogue ECU

Analogue ECU relative

Frequency

Analogue CAN

Up/Down ECU

Up/Down CAN

Analogue ECU

Analogue ECU relative

Frequency

Analogue

CAN

Analogue

CAN

EIC speed demand switch

setup: local normal switch

position.

See the Options H5, H7, H12

and H13 CANbus engine

interface communication

manual for more information.

2793

EIC speed

dem. sw.

Remote norm sw.

Analogue CAN

Up/Down ECU

Up/Down CAN

Analogue ECU

Analogue ECU relative

Frequency

Analogue

CAN

2794

EIC speed

dem. sw.

Remote Emerg. sw.

Analogue CAN

Up/Down ECU

Up/Down CAN

Analogue ECU

Analogue ECU relative

Frequency

Analogue

CAN

2800 Power ramp 3 and 4 (requires option A10)

No. Setting Range Factory

setting

Description

2801 Power ramp

up 3

Ramp up slope 0.1 to 20.0 % 0.1 %

2802

2803

2804

Power ramp

down 3

Power ramp

up 4

Power ramp

down 4

Ramp down slope 0.1 to 20.0 % 0.1 %

Ramp up slope 0.1 to 20.0 % 0.1 %

Ramp down slope 0.1 to 20.0 % 0.1 %

PARAMETER LIST 4189340688R EN Page 202 of 222