1940 Busbar over-voltage 4

No. Setting Range Factory

setting

Description

1941 BB U> 4 Set point 100.0 to 130.0 % 105.0 % The alarm and fail class are

1942 BB U> 4 Timer 1500 to 6000 s 5600 s

activated when the voltage has

been continuously above the

1943 BB U> 4 Relay output A Not used (option

dependent)

Not used programmed value during the

programmed delay.

1944 BB U> 4 Relay output B Not used (option

dependent)

1945 BB U> 4 Enable OFF

ON

Not used

OFF

1946 BB U> 4 Fail class F1 to F9 F2 (Warning)

1300 Busbar under-voltage 1

No. Setting Range Factory

setting

Description

1301 BB U< 1 Set point 40.0 to 100.0 % 97.0 % The alarm and fail class are

1302 BB U< 1 Timer 0.0 to 99.99 s 10.0 s

activated when the voltage has

been continuously under the

1303 BB U< 1 Relay output A Not used (option

dependent)

Not used programmed value during the

programmed delay.

1304 BB U< 1 Relay output B Not used (option

dependent)

1305 BB U< 1 Enable OFF

ON

Not used

OFF

1306 BB U< 1 Fail class F1 to F9 F2 (Warning)

1310 Busbar under-voltage 2

No. Setting Range Factory

setting

Description

1311 BB U< 2 Set point 40.0 to 100.0 % 95.0 % The alarm and fail class are

1312 BB U< 2 Timer 0.0 to 99.99 s 5.0 s

activated when the voltage has

been continuously under the

1313 BB U< 2 Relay output A Not used (option

dependent)

Not used programmed value during the

programmed delay.

1314 BB U< 2 Relay output B Not used (option

dependent)

1315 BB U< 2 Enable OFF

ON

Not used

OFF

1316 BB U< 2 Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 20 of 222