2650 Reactive power control analogue (requires option D1)

No. Setting Range Factory

setting

Description

2651

2652

Q control

Q control

Q Kp

Q Ti

0.00 to 60.00

0.00 to 60.00 s

2.50

1.50 s

PID controller for reactive

power control. The reactive

power control is used for power

factor as well as reactive power

control.

2653 Q control Q Td 0.00 to 2.00 s 0.00 s

These parameters are only

applicable if Analogue or EIC is

selected in parameter 2783.

2660 Reactive power load sharing control analogue (requires option D1)

No. Setting Range Factory

setting

Description

2661 Q load share

ctrl

2662

2663

2664

Q load share

ctrl

Q load share

ctrl

Q load share

ctrl

Q LS Kp

Q LS Ti

Q LS Td

0.00 to 60.00

0.00 to 60.00 s

0.00 to 2.00 s

2.50

1.50 s

0.00 s

The VAr (Q) load sharing is

based on a mix of voltage and

VAr control. Parameter 2664 is

setting the impact of the VAr

controller over the voltage

controller.

Q weight 0.0 to 100.0 % 10.0 %

These parameters are only

applicable if Analogue or EIC is

selected in parameter 2783.

2670 Analogue AVR output offset (requires option D1)

No. Setting Range Factory

setting

Description

2671 Analogue

AVR

2672

2673

2674

Analogue

AVR

Analogue

AVR

Analogue

AVR

Offset 0 to 100 % 50.0 % Sets the offset of the analogue

output when starting the

generator.

Offset 0 to 100 % 50.0 %

Offset 0 to 100 % 50.0 %

Offset 0 to 100 % 50.0 %

These parameters are only

applicable if Analogue or EIC is

selected in parameter 2783.

2690 Voltage control relay (requires option D1)

No. Setting Range Factory

setting

Description

2691 U control U dead band 0.0 to 10.0 % 2.0 % PI controller for voltage control.

2692 U control U Kp 0 to 100 10

These parameters are only

applicable if Relay is selected

in parameter 2783.

2693 U droop relay Droop setting 0 to 10 % 0 %

The droop setting will be

applied on top of the regulation

output.

PARAMETER LIST 4189340688R EN Page 199 of 222