2610 Power ramp up
No. Setting Range Factory
setting
Description
2611 Power ramp
up
2612
2613
Power ramp
up
Power ramp
up
Speed
Delay point
Delay time
0.1 to 20.0 %/s
1 to 100 %
0 to 9900 s
2.0 %/s
10 %
10 s
The delay point determines
when the generator will make a
temporary stop ramping up
after closing of the generator
breaker to preheat the engine
before commencing load
taking.
2614 Island ramp Enable
2615
Power ramp
up
OFF
ON
Steps 0 to 100 1
OFF
If the delay function is not
needed, set this time to 0.
Power % settings relate to
nominal generator power.
2616
Power ramp
up 2
Speed 0.1 to 20.0 %/s 0.1 %/s
Can be activated by parameter
2624 or M-Logic.
With option A10: Ramp 3 and 4
are available in menu 2800.
2620 Power ramp down
No. Setting Range Factory
setting
Description
2621 Power ramp
down
2622
Power ramp
down
Speed 0.1 to 20.0 %/s 3.3 %/s The breaker open point
determines when the Open
breaker relay output is
activated to open the generator
breaker before reaching 0 kW.
Breaker open point 1 to 20 % 5 %
Power % settings relate to
nominal generator power.
2623
Power ramp
down 2
Speed 0.1 to 20.0 %/s 0.1 %/s
Slope of Ramp 2, when
ramping down (not used for
deload).
With option A10: Ramp 3 and 4
are available in menu 2800.
2614
Auto ramp
select
Enable
OFF
ON
ON
ON: Ramp 2 is used with Freq.
dependent P droop.
OFF: Ramp 2 is enabled via M-
Logic.
2640 Voltage control analogue (requires option D1)
No. Setting Range Factory
setting
Description
2641
2642
2643
U control
U control
U control
U Kp
U Ti
U Td
0.00 to 60.00
0.00 to 60.00 s
0.00 to 2.00 s
2.50
1.50 s
0.00 s
PID controller for voltage
control. These parameters are
only applicable if Analogue or
EIC is selected in parameter
2783.
2644 U droop Droop setting 0 to 10 % 0 %
The droop setting will be
applied on top of the regulation
output.
PARAMETER LIST 4189340688R EN Page 198 of 222