2610 Power ramp up

No. Setting Range Factory

setting

Description

2611 Power ramp

up

2612

2613

Power ramp

up

Power ramp

up

Speed

Delay point

Delay time

0.1 to 20.0 %/s

1 to 100 %

0 to 9900 s

2.0 %/s

10 %

10 s

The delay point determines

when the generator will make a

temporary stop ramping up

after closing of the generator

breaker to preheat the engine

before commencing load

taking.

2614 Island ramp Enable

2615

Power ramp

up

OFF

ON

Steps 0 to 100 1

OFF

If the delay function is not

needed, set this time to 0.

Power % settings relate to

nominal generator power.

2616

Power ramp

up 2

Speed 0.1 to 20.0 %/s 0.1 %/s

Can be activated by parameter

2624 or M-Logic.

With option A10: Ramp 3 and 4

are available in menu 2800.

2620 Power ramp down

No. Setting Range Factory

setting

Description

2621 Power ramp

down

2622

Power ramp

down

Speed 0.1 to 20.0 %/s 3.3 %/s The breaker open point

determines when the Open

breaker relay output is

activated to open the generator

breaker before reaching 0 kW.

Breaker open point 1 to 20 % 5 %

Power % settings relate to

nominal generator power.

2623

Power ramp

down 2

Speed 0.1 to 20.0 %/s 0.1 %/s

Slope of Ramp 2, when

ramping down (not used for

deload).

With option A10: Ramp 3 and 4

are available in menu 2800.

2614

Auto ramp

select

Enable

OFF

ON

ON

ON: Ramp 2 is used with Freq.

dependent P droop.

OFF: Ramp 2 is enabled via M-

Logic.

2640 Voltage control analogue (requires option D1)

No. Setting Range Factory

setting

Description

2641

2642

2643

U control

U control

U control

U Kp

U Ti

U Td

0.00 to 60.00

0.00 to 60.00 s

0.00 to 2.00 s

2.50

1.50 s

0.00 s

PID controller for voltage

control. These parameters are

only applicable if Analogue or

EIC is selected in parameter

2783.

2644 U droop Droop setting 0 to 10 % 0 %

The droop setting will be

applied on top of the regulation

output.

PARAMETER LIST 4189340688R EN Page 198 of 222