2570 Frequency control relay output

No. Setting Range Factory

setting

Description

2571 f control relay Dead band 0.2 to 10.0 % 1.0 % These parameters are only

2572 f control relay Kp 0 to 100 10

applicable if Relay is selected

in parameter 2781.

2573 f droop relay Droop setting 0 to 10 % 0 %

The droop setting will be

applied on top of the regulation

output.

2580 Power control relay output

No. Setting Range Factory

setting

Description

2581 P control

relay

2582

P control

relay

Dead band 0.2 to 10.0 % 2.0 % These parameters are only

applicable if Relay is selected

in parameter 2781.

Kp 0 to 100 10

2590 Load sharing control relay output

No. Setting Range Factory

setting

Description

2591 LS ctrl. relay f dead band 0.2 to 10.0 % 1.0 % These parameters are only

2592 LS ctrl. relay LS Kp 0 to 100 10

applicable if Relay is selected

in parameter 2781.

2593 LS ctrl. relay P dead band 0.2 to 10.0 % 2.0 %

2594 LS ctrl. relay P weight 0.0 to 100.0 % 10.0 %

2600 Relay control

No. Setting Range Factory

setting

Description

2601

2602

Relay control

Relay control

GOV ON time

GOV period time

10 to 6500 ms

50 to 32500 ms

500 ms

2500 ms

These parameters are only

applicable if Relay is selected

in parameter 2781.

2603 Relay control

Relay output A Not used (option

(Increase relay) dependent)

Not used

2604 Relay control

Relay output B (Decrease

relay)

Not used (option

dependent)

Not used

NOTE: In the PC utility

software, settings 2603/2604

are found under menu 2602.