4.2 Regulation

2510 Frequency control analogue

No. Setting Range Factory

setting

Description

2511

2512

2513

f control

f control

f control

f Kp

f Ti

f Td

0.00 to 60.00

0.00 to 60.00 s

0.00 to 2.00 s

2.50

1.50 s

0.00 s

PID controller for frequency

control. These parameters are

only applicable if Analogue or

EIC is selected in parameter

2781.

2514 f control Droop setting 0 to 10 % 0 %

The droop setting will be

applied on top of the regulation

output.

2530 Power control analogue

No. Setting Range Factory

setting

Description

2531 P control P Kp 0.00 to 60.00 2.50 PID controller for power

2532 P control P Ti 0.00 to 60.00 s 1.50 s

control. These parameters are

only applicable if Analogue or

2533 P control P Td 0.00 to 2.00 s 0.00 s

EIC is selected in parameter

2781.

2540 Power load sharing control analogue

No. Setting Range Factory

setting

Description

2541 P LS control P LS Kp 0.00 to 60.00 2.50 PID controller for load sharing

2542 P LS control P LS Ti 0.00 to 60.00 s 1.50 s

control. These parameters are

only applicable if Analogue or

2543 P LS control P LS Td 0.00 to 2.00 s 0.00 s

EIC is selected in parameter

2781.

2550 Analogue governor offset

No. Setting Range Factory

setting

Description

2551 Analogue

GOV

2552

2553

Analogue

GOV

Analogue

GOV

Offset

Offset

0 to 100 %

0 to 100 %

50 %

50 %

PID controller for frequency

control. These parameters are

only applicable if Analogue or

EIC is selected in parameter

2781.

Offset 0 to 100 % 50 %

2554

Analogue

GOV

Offset 0 to 100 % 50 %

PARAMETER LIST 4189340688R EN Page 196 of 222