2250 Close before excitation

No. Setting Range Factory

setting

Description

2251 Close bef.

exc.

2252

2253

Close bef.

exc.

Close bef.

exc.

Set point 0 to 4000 RPM 400 RPM If set ON the function will close

the breaker at the selected

Timer 0.0 to 999.0 s 5.0 s

Relay output A

Not used (option

dependent)

Not used

speed. The relay output is used

for the excitation ON signal.

Remember to set the selected

relay in Limit mode.

2254

Close bef.

exc.

Enable

OFF

ON

OFF

2260 Breaker sequence

No. Setting Range Factory

setting

2261 Breaker seq. Break Close GB

Close GB + TB

Close GB

2262 Breaker seq. Timer 0.0 to 999.0 s 5.0 s

2263 Breaker seq. RPM OK 0 to 4000 RPM 1450 RPM

Description

The sequence is used for the

Closed before excitation

function. The excitation will be

activated at the selected speed

in parameter 2263.

2264

Volt.

discharge

Timer 1.0 to 20.0 s 5.0 s

2265 Volt. rerun lvl Set point 30 to 100 % 30 %

2266

ExcCtr

cooldown

Set point

Excitation follow U

busbar

Excitation constant ON

Excitation constant

OFF

Excitation

follow U

busbar

PARAMETER LIST 4189340688R EN Page 195 of 222