2040 Frequency synchronisation control analogue (requires option E1, E2, EF2, EF4, EF5)

No. Setting Range Factory

setting

Description

2041 f sync. f Kp 0.00 to 60.00 2.50 PID controller for dynamic

2042 f sync. f Ti 0.00 to 60.00 s 1.50 s

sync. These parameters are

only applicable if Analogue or

2043 f sync. f Td 0.00 to 2.00 s 0.00 s

EIC is selected in parameter

2780.

2050 Frequency synchronisation control relay

No. Setting Range Factory

setting

Description

2051 f sync. Kp 0 to 100 10 This parameter is only

applicable if Relay is selected

in parameter 2780.

2060 Phase sync. analogue

No. Setting Range Factory

setting

Description

2061 Phase sync. Phase Kp 0.00 to 60.00 0.50 PID controller for static sync.

2062 Phase sync. Phase Ti 0.00 to 60.00 s 3.00 s

These parameters are only

applicable if Analogue or EIC is

2063 Phase sync. Phase Td 0.00 to 2.00 s 0.00 s selected in parameter 2780.

2070 Phase control relay

No. Setting Range Factory

setting

Description

2071 Phase Kp 0 to 100 10 This parameter is only

applicable if Relay is selected

in parameter 2780.

2110 Synchronisation blackout

No. Setting Range Factory

setting

Description

2111 Sync.

blackout

2112

2113

Sync.

blackout

Sync.

blackout

dF min.

dF max.

0.0 to 5.0 Hz

0.0 to 5.0 Hz

3.0 Hz

3.0 Hz

Accepted limits for black

closing of the breaker (or start

of synchronisation) in each

direction of nominal frequency

and voltage.

dU min. 2 to 20 % 5 %

2114

Sync.

blackout

dU max. 2 to 20 % 5 %

2240 Separate synchronisation relay

No. Setting Range Factory

setting

Description

2241 Sep. sync.

relay

2242

Sep. sync.

relay

Relay output A

Relay output B

Not used (option

dependent)

Not used (option

dependent)

Not used

Not used

The output activates during

synchronisation and thereby a

separate synchronising unit

can be activated.

PARAMETER LIST 4189340688R EN Page 194 of 222