No.

Description

9124 Shows the status of the outputs of the unit.

9125 Shows the status of the different lines in M-Logic.

3.9.9 AC configuration

This menu is used to choose the AC configuration. These parameters can also be configured from the utility software.

9130 AC config.

No. Setting Range Factory

setting

Description

9130 AC config. Setting 3 phase L1L2L3

2 phase L1L3

2 phase L1L2

1 phase L1

3 phase

L1L2L3

Phase angles:

• L1L2L3: 120 degrees with

neutral.

• L1L3: 180 degrees (split

phase, neutral in the

centre).

• L1L2: 120 degrees with

neutral.

• L1: Single phase with

phase-neutral.

3.9.10 Angle compensation BB/G

This menu is used to compensate the transformer phase angle when the generator and busbar measurements are made on each

side of a transformer. These parameters can also be configured from the utility software.

9140 Angle comp. BB/G

No. Setting Range Factory

setting

Description

9140 Angle comp.

BB/ G 1

Angle -179.0 to 179.0 ° 0.0

9142

Angle comp.

BB/ G 2

Angle -179.0 to 179.0 ° 0.0

3.9.11 Backlight dimmer

In this menu, it is possible to change the dim of the backlight in the display.

9150 Backlight dim

No. Setting Description

9150 Sets the light intensity for the display.

3.9.12 Application drawing

This menu is used to change between different applications. In the bottom right corner, it is shown which application is active. When

placed on active application, it will say ACT in bottom right corner of the display, otherwise INACT if not placed on active application.

PARAMETER LIST 4189340688R EN Page 188 of 222