04.01.2023 Views

agc-4-parameter-list-4189340688-uk

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

9070 M4 software version

No.

Description

9070 Shows the M4 software version.

9071 Shows the M4 protocol version.

9072 Shows the M4 software revision.

9073 Shows the internal protocol version.

3.9.6 Device type

9100 Device type

No. Setting Range Factory

setting

Description

9100 Device Type DG controller

Mains controller*

BTB controller**

Genset Grp. Tie

controller***

Plant controller***

DG controller

This setting is only accessible

using the JUMP button on the

display.

*Note: A mains controller requires option G5.

**Note: A BTB controller requires option G4 or G5.

***Note: Requires option G7.

CAUTION

The AGC returns to the factory settings when the selection in parameter 9100 is changed.

3.9.7 Password

These parameters can also be configured from the utility software.

911x Password

No. Setting Range Factory

setting

Description

9116 Customer

Password

9117

9118

Service

Password

Master

Password

Setting

Setting

Setting

0 to 32000

0 to 32000

0 to 32000

2000

2001

2002

It is recommended to change

the password levels of the

user, service and master

password if access to

parameter settings must be

restricted.

3.9.8 Service menu

This menu shows the different timer values, the digital in- and outputs, and the status of the different lines in M-Logic.

9120 Service menu

No.

Description

9121 Shows the values of differential timers.

9123 Shows the status of the digital inputs of the unit.

PARAMETER LIST 4189340688R EN Page 187 of 222