3.9 Jump menus
A number of menus can only be entered by using the Jump menu.
3.9.1 Software version
Check the application software version in the unit before contacting DEIF regarding service and support matters. This menu also
shows the clock and the date in the unit.
Option N: W1 displays the IP address and Subnet mask, and W2 displays the Gateway address and software image version.
9000 Software version
Parameter Description Notes
9000
Shows the software version of the unit. Also shows the date and
clock in the unit.
9001 Shows the revision of the software in the unit.
9002 Shows the IP address and the subnet mask. Requires option N
9003 Shows the gateway and the image version of the option N. Requires option N
3.9.2 Display character test
Menu 9010 shows a test print of the character set in the display.
3.9.3 Service port
The service port (9020) can be set up to use the ASCII communication. The ASCII communication is used when the utility software
is connected through a modem.
Selection "0" must be used for cable connection between AGC-4 and a PC. Selection "1" must be used for modem connection
between the AGC-4 and a PC.
3.9.4 Scaling
This parameter can also be configured from the utility software.
9030 Scaling of voltage reference
No. Setting Range Factory
setting
Description
9030 Scaling Setting 10 to 2500 V
100 to 25000 V
10 to 250 kV
0.4 to 75 kV
100 to 25000
V
This parameter is used to scale
the voltage reference.
CAUTION
Changing parameter 9030 affects a number of other parameters (for example, voltages, power, output ranges).
3.9.5 M4 software version
Information about the software version in the engine interface printed circuit board placed in slot 7.
PARAMETER LIST 4189340688R EN Page 186 of 222