04.01.2023 Views

agc-4-parameter-list-4189340688-uk

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

No. Setting Range Factory

setting

Description

14106 Avg. G f< 1 Fail class F1 to F9 F2 (Warning)

ON

14110 Average generator under-frequency 2

No. Setting Range Factory

setting

Description

14111 Avg. G f< 2 Set point 100.0 to 120.0 % 95.0 %

14112 Avg. G f< 2 Timer 0.1 to 100.0 s 5.0 s

14113 Avg. G f< 2 Relay output A

14114 Avg. G f< 2 Relay output B

14115 Avg. G f< 2 Enable

Not used

Option dependent

Not used

Option dependent

OFF

ON

Not used

Not used

OFF

14116 Avg. G f< 2 Fail class F1 to F9 F2 (Warning)

14120 Average over-current 1

No. Setting Range Factory

setting

Description

14121 Avg. I> 1 Set point 50.0 to 200.0 % 115.0 %

14122 Avg. I> 1 Timer 0.1 to 3200.0 s 10.0 s

14123 Avg. I> 1 Relay output A

14124 Avg. I> 1 Relay output B

14125 Avg. I> 1 Enable

Not used

Option dependent

Not used

Option dependent

OFF

ON

Not used

Not used

OFF

14126 Avg. I> 1 Fail class F1 to F9 F2 (Warning)

14130 Average over-current 2

No. Setting Range Factory

setting

Description

14131 Avg. I> 2 Set point 50.0 to 200.0 % 120.0 %

14132 Avg. I> 2 Timer 0.1 to 3200.0 s 5.0 s

14133 Avg. I> 2 Relay output A

14134 Avg. I> 2 Relay output B

14135 Avg. I> 2 Enable

Not used

Option dependent

Not used

Option dependent

OFF

ON

Not used

Not used

OFF

14136 Avg. I> 2 Fail class F1 to F9 F2 (Warning)