04.01.2023 Views

agc-4-parameter-list-4189340688-uk

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

No. Setting Range Factory

setting

Description

14073

Avg. G U< L-N

2

Relay output A

Not used

Option dependent

Not used

14074

Avg. G U< L-N

2

Relay output B

Not used

Option dependent

Not used

14075

Avg. G U< L-N

2

Enable

OFF

ON

OFF

14076

Avg. G U< L-N

2

Fail class F1 to F9 F2 (Warning)

14080 Average generator over-frequency 1

No. Setting Range Factory

setting

Description

14081 Avg. G f> 1 Set point 100.0 to 120.0 % 103.0 %

14082 Avg. G f> 1 Timer 0.1 to 100.0 s 10.0 s

14083 Avg. G f> 1 Relay output A

14084 Avg. G f> 1 Relay output B

14085 Avg. G f> 1 Enable

Not used

Option dependent

Not used

Option dependent

OFF

ON

Not used

Not used

OFF

14086 Avg. G f> 1 Fail class F1 to F9 F2 (Warning)

14090 Average generator over-frequency 2

No. Setting Range Factory

setting

Description

14091 Avg. G f> 2 Set point 100.0 to 120.0 % 105.0 %

14092 Avg. G f> 2 Timer 0.1 to 100.0 s 5.0 s

14093 Avg. G f> 2 Relay output A

14094 Avg. G f> 2 Relay output B

14095 Avg. G f> 2 Enable

Not used

Option dependent

Not used

Option dependent

OFF

ON

Not used

Not used

OFF

14096 Avg. G f> 2 Fail class F1 to F9 F2 (Warning)

14100 Average generator under-frequency 1

No. Setting Range Factory

setting

Description

14101 Avg. G f< 1 Set point 100.0 to 120.0 % 97.0 %

14102 Avg. G f< 1 Timer 0.1 to 100.0 s 10.0 s

14103 Avg. G f< 1 Relay output A

14104 Avg. G f< 1 Relay output B

Not used

Option dependent

Not used

Option dependent

Not used

Not used

14105 Avg. G f< 1 Enable OFF OFF

PARAMETER LIST 4189340688R EN Page 184 of 222