04.01.2023 Views

agc-4-parameter-list-4189340688-uk

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

No. Setting Range Factory

setting

Description

14044

Avg. G U> L-N

1

Relay output B

Not used

Option dependent

Not used

14045

Avg. G U> L-N

1

Enable

OFF

ON

OFF

14046

Avg. G U> L-N

1

Fail class F1 to F9 F2 (Warning)

14050 Average generator over-voltage L-N 2

No. Setting Range Factory

setting

Description

14051 Avg. G U> L-N

2

Set point 100.0 to 120.0 % 105.0 %

14052

Avg. G U> L-N

2

Timer 0.1 to 100.0 s 5.0 s

14053

Avg. G U> L-N

2

Relay output A

Not used

Option dependent

Not used

14054

Avg. G U> L-N

2

Relay output B

Not used

Option dependent

Not used

14055

Avg. G U> L-N

2

Enable

OFF

ON

OFF

14056

Avg. G U> L-N

2

Fail class F1 to F9 F2 (Warning)

14060 Average generator under-voltage L-N 1

No. Setting Range Factory

setting

Description

14061 Avg. G U< L-N

1

Set point 100.0 to 120.0 % 97.0 %

14062

Avg. G U< L-N

1

Timer 0.1 to 100.0 s 10.0 s

14063

Avg. G U< L-N

1

Relay output A

Not used

Option dependent

Not used

14064

Avg. G U< L-N

1

Relay output B

Not used

Option dependent

Not used

14065

Avg. G U< L-N

1

Enable

OFF

ON

OFF

14066

Avg. G U< L-N

1

Fail class F1 to F9 F2 (Warning)

14070 Average generator under-voltage L-N 2

No. Setting Range Factory

setting

Description

14071 Avg. G U< L-N

2

Set point 100.0 to 120.0 % 95.0 %

14072

Avg. G U< L-N

2

Timer 0.1 to 100.0 s 5.0 s

PARAMETER LIST 4189340688R EN Page 183 of 222