No. Setting Range Factory

setting

Description

14015

Avg. G U> L-L

2

Enable

OFF

ON

OFF

14016

Avg. G U> L-L

2

Fail class F1 to F9 F2 (Warning)

14020 Average generator under-voltage L-L 1

No. Setting Range Factory

setting

Description

14021 Avg. G U< L-L

1

Set point 100.0 to 120.0 % 97.0 %

14022

Avg. G U< L-L

1

Timer 0.1 to 100.0 s 10.0 s

14023

Avg. G U< L-L

1

Relay output A

Not used

Option dependent

Not used

14024

Avg. G U< L-L

1

Relay output B

Not used

Option dependent

Not used

14025

Avg. G U< L-L

1

Enable

OFF

ON

OFF

14026

Avg. G U< L-L

1

Fail class F1 to F9 F2 (Warning)

14030 Average generator under-voltage L-L 2

No. Setting Range Factory

setting

Description

14031 Avg. G U< L-L

2

Set point 100.0 to 120.0 % 95.0 %

14032

Avg. G U< L-L

2

Timer 0.1 to 100.0 s 5.0 s

14033

Avg. G U< L-L

2

Relay output A

Not used

Option dependent

Not used

14034

Avg. G U< L-L

2

Relay output B

Not used

Option dependent

Not used

14035

Avg. G U< L-L

2

Enable

OFF

ON

OFF

14036

Avg. G U< L-L

2

Fail class F1 to F9 F2 (Warning)

14040 Average generator over-voltage L-N 1

No. Setting Range Factory

setting

Description

14041 Avg. G U> L-N

1

Set point 100.0 to 120.0 % 103.0 %

14042

Avg. G U> L-N

1

Timer 0.1 to 100.0 s 10.0 s

14043

Avg. G U> L-N

1

Relay output A

Not used

Option dependent

Not used

PARAMETER LIST 4189340688R EN Page 182 of 222